Product details

Santak Castle Series rack-mounted UPS is designed for critical equipment, featuring pure online double-conversion technology that achieves zero-switching between utility and battery modes, delivering pure sine wave power. The product covers a power range of 1-10kVA with an output power factor up to 0.9, providing 28% more effective power compared to traditional equipment. Ultra-wide 110-300VAC input voltage range adapts to areas with poor power quality and supports generator connection, effectively isolating power fluctuations. Flexible long-run battery solutions offer up to 12 hours of backup protection, while the unique 2U compact design saves 40% cabinet space.Built-in intelligent management system supports multiple communication protocols such as USB/RS232/network, compatible with virtualization platforms like VMware, enabling remote monitoring via mobile devices. The product is CE certified and meets IEEE standards, capable of operating at 50°C high temperatures, with 12A fast charging technology and a quiet mode as low as 40 decibels, providing 24/7 stable power for financial outlets, automated production lines, and medical equipment.

Product Features

  • Pure online double-conversion technology achieves zero-switch between utility and battery modes, outputting clean sine waves to effectively protect sensitive equipment
  • 2U compact rack design saves 40% installation space, supports N+X parallel redundancy configuration to enhance overall system reliability
  • Ultra-wide 110-300VAC input range adapts to harsh grid environments, with built-in 50°C high-temperature resistant components ensuring stable operation under extreme conditions
  • Smart monitoring system supports USB/RS232/network communication protocols, compatible with VMware virtualization platforms for remote mobile management
  • 12A fast charging technology paired with long-life battery packs provides up to 12-hour backup runtime, CE certified and compliant with IEEE industrial standards

Application Scenarios

  • Suitable for precision imaging equipment like medical CT scanners and MRI machines, eliminating diagnostic errors caused by voltage fluctuations
  • Ensures 24/7 uninterrupted operation of bank core network equipment and ATM terminals to prevent financial transaction disruptions
  • Provides power filtering for 5G base station BBU equipment and transmission nodes to ensure zero packet loss in communication networks
  • Supports industrial robot servo systems and PLC control cabinets to maintain continuous production line operation during voltage fluctuations
  • Protects scientific research spectrometers and electron microscopes from power harmonic interference to ensure accurate experimental data

Product Parameters

  • Model:C2KR (2021)
  • Rated capacity:2kVA
  • Input voltage:(110-300)VAC
  • Input frequency:40-70Hz
  • Input power factor:≥0.98
  • External battery nominal voltage:-
  • Battery type:Valve-regulated lead-acid battery
  • Number of batteries:4PCS
  • Output voltage:220*(1±2%)VAC
  • Output frequency:Synchronized with input (utility mode) 50±0.05Hz (battery mode)
  • Output power factor:0.8 at 40°C ambient temperature, 0.9 at 30°C ambient temperature
  • Overload capability:105%-150%, 47s-25s; 150%-200%, 25s-300ms; above 200%, 200ms (output power factor 0.8)
  • Outlet type * quantity:National standard socket*2
  • Transfer time (power failure/recovery):0ms
  • Backup time (80% load, 0.8 power factor):>4.5 min
  • Indicator LED+LCD:LCD display for voltage, frequency, etc., UPS operation status indicators
  • Alarm sound (battery discharge):Beeps every four seconds when input power fails, beeps every second when battery is about to run out
  • Alarm sound (UPS abnormal):Continuous beep
  • Auto restart:Automatic restart when utility power is restored after battery shutdown
  • Communication interface USB:Monitoring function
  • Expandable communication card (optional):NMC card, CMC card, AS400 card, SPCC card
  • Temperature:0°C-40°C
  • Humidity:<95%
  • Main unit weight (net) Kg:17.5
  • Battery module weight (net) Kg:-
  • Main unit installation dimensions:438*570*87
  • Battery module dimensions W*D*H(mm):-
  • Main unit shipping weight (gross) Kg:20.9
  • Battery module shipping weight (gross) Kg:-
  • Main unit shipping dimensions W*D*H (mm):580*760*220
  • Battery module dimensions W*D*H (mm):-