Product details

The Santek Castle Series SCC008UCE1/PE1 fixed-frequency precision air conditioner is an intelligent temperature control solution specifically designed for small and medium-sized equipment room environments. The unit adopts a high air volume and small enthalpy difference design, with a sensible heat ratio of up to 0.9, precisely matching the high heat load characteristics of equipment rooms. Paired with a dual variable-frequency system of EC centrifugal fans and speed-adjustable axial fans, it achieves a national first-level energy-saving standard with an annual energy efficiency ratio of 4.0. The unit's core configuration includes an efficient fixed-frequency compressor and electronic expansion valve, supporting operation in conventional environments from -15℃ to 45℃. With optional low-temperature components, it can also provide stable cooling in extreme cold conditions as low as -35℃ in northern regions, meeting the demands of harsh scenarios such as rail transit.The intelligent control system is equipped with a 4.3-inch LCD touchscreen, supports 500 operation log entries storage and self-diagnosis functions, and enables group control management of up to 32 units via RS-485 interface. The innovative quick-connect piping design eliminates welding, while the integrated air hood structure and pre-charged refrigerant process increase installation efficiency by 40%, supporting flexible right/bottom piping layouts. Standard dust filters and leak detection provide protection, with PTC ceramic heating and electrode humidification modules ensuring precise temperature and humidity control at ±1℃/±5%RH for constant models.The compact unit (550×450×1800mm) fits small spaces like equipment rooms and UPS rooms, featuring a CRAA-certified black metal shell, suitable for 24/7 environmental protection in critical facilities such as communication base stations, data centers, and financial server rooms.

Product Features

  • High air volume with small enthalpy difference design combined with 0.9 high sensible heat ratio, precisely matching the high heat load characteristics of server rooms, achieving national first-class energy efficiency standards with dual-frequency EC centrifugal fan and speed-adjustable axial fan system
  • Electronic expansion valve precision temperature control maintains fluctuations within ±1°C, with standard PTC ceramic heating and electrode humidification modules ensuring ±5%RH humidity accuracy in constant temperature & humidity models
  • Pre-charged R410A eco-friendly refrigerant with quick-connect piping eliminates welding, while integrated air hood boosts installation efficiency by 40% and supports flexible right/bottom piping layouts
  • Equipped with -35°C low-temperature components to overcome extreme cold, featuring full-front maintenance design and compact 550mm-wide body for confined spaces like equipment rooms/UPS rooms
  • 4.3-inch smart touchscreen supports 32-unit group control, RS-485 interface enables remote monitoring, with 500-operation log storage and self-diagnosis for maintenance efficiency

Application Scenarios

  • 5G base station power equipment cooling solution, ensuring stable operation across outdoor -35°C to 45°C temperature ranges
  • Constant temperature control for urban rail transit electronic equipment rooms, adapted to vibration environments and high-density heat loads
  • Medical imaging server environment maintenance, safeguarding precision equipment with ±1°C temperature and humidity stability
  • Industrial automation control center cooling, designed for workshop dust environments and continuous operation conditions
  • Cloud computing edge node room thermal management, adapted to compact spaces of micro data centers and intelligent group control requirements

Product Parameters

  • Model:SCC008UCE1/PE1
  • System Specifications Function:Cooling Only/Constant Temperature & Humidity
  • System Specifications Total Cooling Capacity (KW) (Return Air 24℃, RH50%):7.5
  • System Specifications Airflow:2360
  • System Specifications Sensible Heat Ratio:0.9
  • System Specifications Annual Energy Efficiency Ratio:4
  • System Specifications Air Supply Method:Top Front Air Supply
  • Compressor Compressor Type:Fixed Frequency Compressor
  • Compressor Refrigerant:R410A
  • Compressor Pre-charged Refrigerant Support Pipe Length (m):5
  • Heating (Constant Temperature Models Only) Electric Heating Type:PTC Ceramic
  • Heating (Constant Temperature Models Only) Heating Capacity (kW):3
  • Heating (Constant Temperature Models Only) Heater Stages:1
  • Humidification (Constant Temperature Models Only) Humidification Type:Electrode
  • Humidification (Constant Temperature Models Only) Humidification Capacity (kg/hr):3
  • Humidification (Constant Temperature Models Only) Humidification Water Inlet Thread:G1/2 Internal Thread
  • Expansion Valve Expansion Valve Type:Electronic Expansion Valve
  • HMI Display:4.3-inch LCD Display
  • HMI Standard Communication Interface:RS485
  • Indoor Unit Parameters Power Input:380V/3 Phase/50Hz
  • Indoor Unit Parameters Fan Type:EC Fan
  • Indoor Unit Parameters Exterior Color:Black
  • Indoor Unit Parameters Unit Dimensions Width*Depth*Height (mm):550*450*1800
  • Indoor Unit Parameters Net Weight (kg):112/118
  • Outdoor Unit Parameters Model:CS010F
  • Outdoor Unit Parameters Power Input:220V/Single Phase
  • Outdoor Unit Parameters Fan Type:AC Axial Fan
  • Outdoor Unit Parameters Outdoor Unit Color:White
  • Outdoor Unit Parameters Unit Dimensions Width*Depth*Height (mm):728*405*762
  • Outdoor Unit Parameters Net Weight (kg):34
  • Other Function Settings Group Control:Supported
  • Other Function Settings Leak Detection:Standard
  • Other Function Settings Extension Kit:Optional
  • Other Function Settings Low Temperature Kit:Optional
  • Installation Requirements Indoor/Outdoor Unit Pipe Length (Standard/With Extension Kit) (m):20/45
  • Installation Requirements Height Difference (+/-) (m):10/-5
  • Certification:CCC, CQC, CRAA
  • Warranty:One Year