Product details

Santak SPU 12kVA Power-Specific UPS adopts a dual-isolation architecture design, meeting the stringent requirements of power systems for power supply reliability. The device directly connects to the DC power system (110/220VDC) of power plants/substations, effectively preventing reverse current through check diodes, reducing battery investment and maintenance costs. The input side supports three-phase 380V±25% or single-phase 220V±25% voltage fluctuations, with output waveform distortion below 3% and efficiency over 83%, capable of handling complex power demands of IT equipment, nonlinear loads, and impact loads.Built-in multi-protection mechanisms include automatic shutdown for low battery voltage, overload bypass switching, short-circuit current limiting, etc. With EMC filters, it is certified by EN50091-2, ensuring stable operation in wide-temperature environments from -15°C to 55°C. Widely applicable in scenarios like booster stations and dispatch communication systems, providing comprehensive power protection compliant with industry standards for the power sector.

Product Features

  • Adopts DC bus direct connection design, enabling access to power system DC power without external charging modules
  • Dual isolation architecture achieves complete electrical isolation between input and output, enhancing system safety and anti-interference capability
  • Wide voltage input range supports three-phase 380V±25% and single-phase 220V±25% voltage fluctuation adaptation
  • Built-in check diode prevents current backflow, reducing DC system maintenance costs and safety risks
  • DL/T5491 and DL/T1074 dual industry certifications ensure compliance with stringent power system operational standards

Application Scenarios

  • Core equipment for uninterrupted power supply in digital electro-hydraulic control (DEH) systems of power plants
  • Critical power solution for 24/7 operation of substation dispatch communication systems
  • Power support platform for precision instruments and automation control equipment in household step-down stations
  • Reliable power deployment solution for electrical equipment in high-dust/corrosive industrial environments
  • Core power supply unit for redundant configuration scenarios in DC bus-based power systems

Product Parameters

  • Model:Power-specific UPS SPU 12kVA
  • Rated Capacity:12kVA
  • DC Source (DC220V):Y
  • DC Source (DC110V):Y
  • Input AC Single Phase (1P):Y(1P2W)
  • Input Voltage:220V±25%
  • Input AC Three Phase (3P):Y (3P4W)
  • Input Voltage:380V±25%
  • Input Frequency:50Hz/60Hz ±10%
  • Input DC Voltage and Range:DC220V (Rated) DC180V~DC270V DC110V (Rated) DC90~DC135V
  • Output Voltage and Accuracy:AC220±1% (1P2W)
  • Output Frequency:50Hz/60Hz ±0.1%
  • Output Waveform Distortion Rate:<3% (Linear Load), <5% (Non-linear Load)
  • Output Overload Capacity:<=100% Continuous Load 100%~120% 10 Minutes Transfer to Bypass 120%~150%, 60 Seconds Transfer to Bypass ≥150%, 1 Second Transfer to Bypass
  • Output Power Factor:0.7
  • Output Crest Factor:0.125694444
  • Output Efficiency:≥83%
  • Protection Function Battery:Battery Low Voltage Auto Shutdown, Circuit Breaker Protection
  • Protection Function Overload Capacity:Transfer to bypass after overload, automatically recover after load reduction
  • Protection Function Short Circuit:Current limit auto shutdown, fuse and circuit breaker protection
  • Protection Function Fault:Fault or internal overtemperature, automatically transfer to bypass and alarm
  • Protection Function Frequency:50Hz/60Hz ±10%
  • Protection Function EMI/EMC:EN50091-2 Approved (optional filter)
Loading...