Santak SPU 12kVA Power-Specific Uninterruptible UPS Power Supply 12kVA
Santak SPU 12kVA Power-Specific UPS is designed for power systems such as power plants and substations, compliant with DL/T5491-2014 and DL/T1074-2019 industry standards. It supports DC bus input and dual-isolation structure, adapting to high-dust/wide-temperature/high-humidity environments, ensuring continuous power supply for critical loads like DCS and DEH.
Buy Now
- WeChat:13775032303
- Email:powercube@foxmail.com
Product details
Santak SPU 12kVA Power-Specific UPS adopts a dual-isolation architecture design, meeting the stringent requirements of power systems for power supply reliability. The device directly connects to the DC power system (110/220VDC) of power plants/substations, effectively preventing reverse current through check diodes, reducing battery investment and maintenance costs. The input side supports three-phase 380V±25% or single-phase 220V±25% voltage fluctuations, with output waveform distortion below 3% and efficiency over 83%, capable of handling complex power demands of IT equipment, nonlinear loads, and impact loads.Built-in multi-protection mechanisms include automatic shutdown for low battery voltage, overload bypass switching, short-circuit current limiting, etc. With EMC filters, it is certified by EN50091-2, ensuring stable operation in wide-temperature environments from -15°C to 55°C. Widely applicable in scenarios like booster stations and dispatch communication systems, providing comprehensive power protection compliant with industry standards for the power sector.
Product Features
- Adopts DC bus direct connection design, enabling access to power system DC power without external charging modules
- Dual isolation architecture achieves complete electrical isolation between input and output, enhancing system safety and anti-interference capability
- Wide voltage input range supports three-phase 380V±25% and single-phase 220V±25% voltage fluctuation adaptation
- Built-in check diode prevents current backflow, reducing DC system maintenance costs and safety risks
- DL/T5491 and DL/T1074 dual industry certifications ensure compliance with stringent power system operational standards
Application Scenarios
- Core equipment for uninterrupted power supply in digital electro-hydraulic control (DEH) systems of power plants
- Critical power solution for 24/7 operation of substation dispatch communication systems
- Power support platform for precision instruments and automation control equipment in household step-down stations
- Reliable power deployment solution for electrical equipment in high-dust/corrosive industrial environments
- Core power supply unit for redundant configuration scenarios in DC bus-based power systems
Product Parameters
- Model:Power-specific UPS SPU 12kVA
- Rated Capacity:12kVA
- DC Source (DC220V):Y
- DC Source (DC110V):Y
- Input AC Single Phase (1P):Y(1P2W)
- Input Voltage:220V±25%
- Input AC Three Phase (3P):Y (3P4W)
- Input Voltage:380V±25%
- Input Frequency:50Hz/60Hz ±10%
- Input DC Voltage and Range:DC220V (Rated) DC180V~DC270V DC110V (Rated) DC90~DC135V
- Output Voltage and Accuracy:AC220±1% (1P2W)
- Output Frequency:50Hz/60Hz ±0.1%
- Output Waveform Distortion Rate:<3% (Linear Load), <5% (Non-linear Load)
- Output Overload Capacity:<=100% Continuous Load 100%~120% 10 Minutes Transfer to Bypass 120%~150%, 60 Seconds Transfer to Bypass ≥150%, 1 Second Transfer to Bypass
- Output Power Factor:0.7
- Output Crest Factor:0.125694444
- Output Efficiency:≥83%
- Protection Function Battery:Battery Low Voltage Auto Shutdown, Circuit Breaker Protection
- Protection Function Overload Capacity:Transfer to bypass after overload, automatically recover after load reduction
- Protection Function Short Circuit:Current limit auto shutdown, fuse and circuit breaker protection
- Protection Function Fault:Fault or internal overtemperature, automatically transfer to bypass and alarm
- Protection Function Frequency:50Hz/60Hz ±10%
- Protection Function EMI/EMC:EN50091-2 Approved (optional filter)