Product details

The Santak Castle 3C3 HD-300K is a fully upgraded product from Santak's classic series, specifically designed for medium to large-scale power protection needs. This UPS adopts three-level IGBT technology and optimized circuit design, achieving up to 97% efficiency in online mode and 99% in ECO energy-saving mode, significantly reducing energy costs. Its output power factor is improved to 1.0, with a 10% increase in effective load capacity compared to traditional equipment, meeting the demands of high-power scenarios such as data centers and industrial production. The modular internal design greatly reduces maintenance time (MTTR<30 minutes), equipped with a 7-inch smart touchscreen for visual operation, supporting parallel operation of up to 4 units and battery sharing, ensuring system expansion flexibility.The built-in intelligent battery management system supports various energy storage solutions including lead-acid, gel, and lithium batteries, with a maximum charging current of 400A, enabling rapid recovery of backup power. The product has passed multiple safety certifications and is suitable for wide-temperature environments ranging from -15°C to 55°C, making it ideal for areas with stringent power continuity requirements such as hospital operating rooms, financial data centers, and 5G communication base stations, providing zero-interruption protection for critical equipment.

Product Features

  • Next-gen IGBT three-level technology achieves 97% online efficiency and 99% ECO mode, significantly reducing energy costs
  • 1.0 output power factor increases effective load capacity by 10%, meeting stable operation requirements of high-power equipment
  • Modular structural design enables MTTR<30min rapid maintenance, equipped with 7-inch smart touchscreen to streamline operations
  • Supports parallel operation of 4 units and battery pack sharing solutions for flexible expansion of power supply capacity
  • Compatible with lead-acid/gel/lithium batteries and supports 400A high-current charging, meeting diverse energy storage configuration needs

Application Scenarios

  • Ensures zero-interruption power supply for hospital operating room life support systems and ICU equipment
  • Provides a pure power environment with voltage stabilization and surge protection for precision laboratory instruments in higher education institutions
  • Supports continuous operation of smart manufacturing production lines, preventing production interruptions caused by voltage fluctuations
  • Meets the stringent requirements of 5G communication base station core rooms for power redundancy and wide-temperature environments
  • Ensures 24/7 stable operation of financial transaction systems and data center server clusters

Product Parameters

  • Model:3C3 HD-300K
  • Rated Capacity:300KVA/300KW
  • Input Mode:Three-phase + Neutral + Ground
  • Input Frequency:50/60Hz, range 42 - 70Hz
  • Input Power Factor:≥ 0.99
  • Input Mains Voltage Range:240 ~ 478Vac line voltage; 138 ~ 276Vac phase voltage
  • Input Bypass Voltage Range:340 ~ 438Vac line voltage; 196 ~ 253Vac phase voltage
  • Input Current Harmonic:<3% (rated input linear load)
  • Output Rated Voltage:230/400Vac, 3-phase+N+PE, (220/380, 240/415 optional)
  • Output Power Factor:1.0*
  • Rated output frequency:50Hz (default) or 60Hz
  • Output frequency variation rate:1Hz/s
  • Maximum output waveform distortion:<1% (100% linear load)
  • Output overload time:102 ~ 110% load for 60 minutes, 111 ~ 125% load for 10 minutes, 126 ~ 150% load for 1 minute
  • Online double conversion mode efficiency:Up to 97%
  • ECO energy-saving mode efficiency:Up to 99%
  • Battery type:VRLA lead-acid battery, AGM, gel battery, NiCad battery, lithium battery
  • Battery voltage:480V (40 cells) to 690V (50 cells), default 40 cells
  • Charging method:Intelligent battery management
  • Maximum charging current:200A
  • Parallel capability:Parallel connection of 4 units
  • Ambient temperature:0 ~ 40°C
  • Storage temperature:–15 ~ +55°C
  • Ambient humidity:5 ~ 95%, non-condensing
  • Altitude:No derating required below 1000m altitude; derate according to GB/T 3859.2 if exceeding 1000m
  • Width*Depth*Height (mm):1100*1000*2000
  • Net weight (excluding battery):600kg
  • Gross weight (excluding battery):700kg
  • Safety compliance standards:GB4943; YD/T1095; GB/7260.2; IEC/62040-2